Written by IAPMO 9:16 pm Uniform Codes Spotlight

UNIFORM CODES SPOTLIGHT

July 31, 2025

From the 2024 UPC Illustrated Training Manual, Chapter 9, VENTS

908.1 Vertical Wet Venting. Wet venting is limited to vertical drainage piping receiving the discharge from the trap arm of one and two fixture unit fixtures that also serves as a vent not exceeding four fixtures. Wet-vented fixtures shall be within the same story; provided, further, that fixtures with a continuous vent discharging into a wet vent shall be within the same story as the wet-vented fixtures. No wet vent shall exceed 6 feet (1829 mm) in developed length.

FIGURE 908.1B
WET VENT SIZING EXAMPLE 2
FIGURE 908.1A
WET VENT SIZING EXAMPLE 1

From the 2024 UMC Illustrated Training Manual, Chapter 6, DUCT SYSTEMS

603.4 Flexible Air Ducts. Flexible air ducts shall comply with UL 181, and shall be installed in accordance with the manufacturer’s installation instructions and SMACNA HVAC Duct Construction Standards – Metal and Flexible. Flexible air duct installations shall comply with the following:

(1) Ducts shall be installed using the minimum required length to make the connection.

(2) Horizontal duct runs shall be supported at not more than 4 feet (1219 mm) intervals.

(3) Vertical risers shall be supported at not more than 6 feet (1829 mm) intervals.

(4) Sag between support hangers shall not exceed 1/2 inch (12.7 mm) per foot (305 mm) of support spacing.

(5) Supports shall be rigid and shall be not less than 1 1/2 inches (38 mm) wide at point of contact with the duct surface.

(6) Duct bends shall be not less than one duct diameter bend radius.

(7) Screws shall not penetrate the inner liner of non-metallic flexible ducts unless permitted in accordance with the manufacturer’s installation instructions.

(8) Fittings for attaching non-metallic ducts shall be beaded and have a collar length of not less than 2 inches (51 mm) for attaching the duct. Metal worm-gear clamps shall be used.

Exception: Where attaching metallic ducts using screws in accordance with the manufacturer’s installation instructions.

(9) Duct inner liner shall be installed at not less than 1 inch (25.4 mm) on the collar and past the bead prior to the application of the tape and mechanical fastener. Where mastic is used instead of tape, the mastic shall be applied in accordance the mastic manufacturer’s instructions.

(10) Duct outer vapor barriers shall be secured using two wraps of approved tape. A mechanical fastener shall be permitted to be used in place of, or in combination with, the tape.

(11) Flexible air ducts shall not penetrate a fire-resistance rated assembly or construction.

(12) The temperature of the air to be conveyed in a flexible air duct shall not exceed 250°F (121°C).

(13) Flexible air ducts shall be sealed in accordance with Section 603.9.

(This is not to be considered the official position of IAPMO, nor is it an official interpretation of the Codes.)

IAPMO

IAPMO develops and publishes the Uniform Plumbing Code®,the most widely recognized code of practice used by the plumbing industry worldwide; Uniform Mechanical Code®; Uniform Swimming Pool, Spa and Hot Tub Code®; and Uniform Solar Energy, Hydronics and Geothermal Code — the only plumbing, mechanical, solar energy and swimming pool codes designated by ANSI as American National Standards — and the Water Efficiency Standard (WE-Stand)™. IAPMO works with government, contractors, labor force, and manufacturers to produce product standards, technical manuals, personnel certification/educational programs and additional resources in order to meet the ever-evolving demands of the industry in protecting public health and safety.

Last modified: July 31, 2025

Close